Class A, Style 6 Wiring Configuration

Figure 8. Example of Class A, Style 6 Requiring CA-6075

Notes:

1. The Class A, Style 6 configuration does not provide the level of protection as Class A, Style 7.

2. Class A, Style 7 requires installation of a CA-6075.

3. The use of a SCI or AIB is not required.

4. The SLC connection requires that the wires are separated 10’, installed in conduit or other mechanical protection.

5. Maximum wiring resistance must not exceed 50 ohms.

Class A, Style 7 Wiring Configuration

Figure 9. Example of SLC Wiring - Class A, Style 7 Requiring CA-6075

Address No.

Potter Electric Signal Company

FIRE ALARM EQUIP

MENT

XXXX

Address No.

Potter Electric Signal Company

FIRE ALARM EQUIP

MENT

XXXX

24- 24+ S- S+

B- B+ A- A+

Conventional Initiating Zone Module

Model No. CIZM-4

Ser. No. xxxxxx

Document: TN51313e date:XX.XX.2009

Compatibility Identifier: INTE01
WARNING :

Power supply for terminals 24+ and 24- must

be power limited

All Terminals are power limited.

S- S+

Z2

C2

Z1

C1

NO2

(NC2)

NO1

(NC1)

Dual Contact Module

Model No. DCM-4

Ser. No. xxxxxx

Document: TN51316e date:XX.XX.2009

WARNING :

All Terminals are power limited.

SIGNALING

LISTED

L

U

SIGNALING

LISTED

L

U

PFC-6000

Series

SLC Loop (Class A Style 7)

Terminal Connections

5.1kΩ

5.1kΩ

5.1kΩ

Address No.

Potter Electric Signal Company

FIRE ALARM EQUIP

MENT

XXXX

S-1 S+1

Short Circuit Isolater

Model No. SCI

Ser. No. xxxxxx

Document: TN51313e date:XX.XX.2009

WARNING :

All Terminals are power limited.

SIGNALING

LISTED

L

U

S-2 S+2

Address No.

Potter Electric Signal Company

FIRE ALARM EQUIP

MENT

XXXX

S-1 S+1

Short Circuit Isolater

Model No. SCI

Ser. No. xxxxxx

Document: TN51313e date:XX.XX.2009

WARNING :

All Terminals are power limited.

SIGNALING

LISTED

L

U

S-2 S+2

Address No.

Potter Electric Signal Company

FIRE ALARM EQUIP

MENT

XXXX

S-1 S+1

Short Circuit Isolater

Model No. SCI

Ser. No. xxxxxx

Document: TN51313e date:XX.XX.2009

WARNING :

All Terminals are power limited.

SIGNALING

LISTED

L

U

S-2 S+2

Address No.

Potter Electric Signal Company

FIRE ALARM EQUIP

MENT

XXXX

S-1 S+1

Short Circuit Isolater

Model No. SCI

Ser. No. xxxxxx

Document: TN51313e date:XX.XX.2009

WARNING :

All Terminals are power limited.

SIGNALING

LISTED

L

U

S-2 S+2

DWG #593-9

SCI

SCI

SCI

SCI

Notes:

1. The Class A, Style 7 requires installation of an isolator close nipple connected to every module or sensor.

Isolators may be either a SCI or an AIB addressable base.

2. Class A, Style 7 requires installation of a CA-6075.

3. The SLC connection requires that the wires are separated by a minimum of 10’ and installed in conduit or other

mechanical protection.

4. Maximum wiring resistance must not exceed 50 ohms.

S- S+ C

NO

(NC)

Potter Electric Signal Company

Miniature Contact Module

Model No. MCM

Ser. No. xxxxxx

Document:

TN51314e date: XX.XX.2009

WARNING:

All Terminals are power limited

Address No.

SIGNALING

LISTED

L

U

FIRE ALARM EQUIPMENT

XXXX

Address No.

Potter Electric Signal Company

SIGNALING

LISTED

L

U

FIRE ALARM EQUIP

MENT

XXXX

24-

Address No.

Potter Electric Signal Company

FIRE ALARM EQUIP

MENT

XXXX

Address No.

Potter Electric Signal Company

FIRE ALARM EQUIP

MENT

XXXX

Address No.

Potter Electric Signal Company

FIRE ALARM EQUIP

MENT

XXXX

Address No.

Potter Electric Signal Company

FIRE ALARM EQUIP

MENT

XXXX

24+ S- S+

Monitored Output Module

Model No. MOM-4

Ser. No. xxxxxx

A- A+

Document: TN51318e date:XX.XX.2009
WARNING :

Power supply for terminals 24+ and 24- must

be power limited.

All Terminals are power limited.

NC2 C2 NO2 NC1 C1 NO1

S-

Twin Relay Module

Model No. TRM-4

Ser. No. xxxxxx

Document: TN51317e date:XX.XX.2009
WARNING :

Terminals S+, S- are power limited.

Terminals NO1, C1, NC1, NO2, C2, NC2 are

non power limited

S+

Single Contact Module

Model No. SCM-4

Ser. No. xxxxxx

Document: TN51315e date:XX.XX.2009

WARNING :

All Terminals are power limited.

S- S+

Z NO C

24- 24+ S- S+

B- B+ A- A+

Conventional Initiating Zone Module

Model No. CIZM-4

Ser. No. xxxxxx

Document: TN51313e date:XX.XX.2009

Compatibility Identifier: INTE01
WARNING :

Power supply for terminals 24+ and 24- must

be power limited

All Terminals are power limited.

S- S+

Z2

C2

Z1

C1

NO2

(NC2)

NO1

(NC1)

Dual Contact Module

Model No. DCM-4

Ser. No. xxxxxx

Document: TN51316e date:XX.XX.2009

WARNING :

All Terminals are power limited.

SIGNALING

LISTED

L

U

SIGNALING

LISTED

L

U

SIGNALING

LISTED

L

U

SIGNALING

LISTED

L

U

PFC-6000

Series

SLC Loop (Class A)

Terminal Connections

3

6

7

8

5.1kΩ

5.1kΩ

5.1kΩ

5.1kΩ

5.1kΩ

5.1kΩ

5.1kΩ

5.1kΩ

DWG #593-8

Advertising