Potter PFC-6075R User Manual

Page 24

Advertising
background image

3-18

PFC-6075R • 5403594 • REV D • 9/14

Miniature Contact Module (MCM)

Refer to the figure shown below for a MCM wiring example.

Figure 13. MCM Wiring Example

COM

NO

S-

S+

5.1KΩ 1/2W EOLR

SLC Loop

To Next Module

From FACP or Previous Module

Note: The resistance of external wiring shall be less that 100Ω.

The capacitance of external wiring shall be less than 1 micro farads.

Mini Contact Module

Model No. MCM

DWG #593-13

Note: If MCM is located in an electrical box, it should be secured using crew tabs or other method to prevent movement.

Single Contact Module – 4 inch Mount (SCM-4)
Refer to the figure shown below for a SCM-4 wiring example.

Figure 14. SCM-4 Wiring Example

COM

NO

S-

S+

SLC Loop

To Next Module

From FACP or Previous Module

Single Contact Module

Model No. SCM-4

5.1KΩ 1/2W EOLR

Note: The resistance of external wiring shall be less that 100Ω.

The capacitance of external wiring shall be less than 1 micro farads.

Z

LED

DWG #593-14

Dual Contact Module – 4 inch Mount (DCM-4)
Refer to the figure shown below for a Class A DCM-4 wiring example.

Figure 15. DCM-4 with One Class A Circuit

S-

S+

SLC Loop

To Next Module

From FACP or Previous Module

Dual Contact Module

Model No. DCM-4

LED

Note: The resistance of external wiring shall be less that 100Ω.

The capacitance of external wiring shall be less than 1 micro farads.

JP1

Select Style 6

NO1

C1

Z1

NO2

C2

Z2

DWG #593-15

Note: In this configuration, the DCM-4 operates as a single point Class A module.