Table 9: Programming Options

Topic

Feature or

Option

Permitted

in UL (Y/N)

Possible Settings

Setting(s) Permitted

in UL864?

Comment

SLC Point

Function

Y

Photo Detector (PSA)

Photo Duct Detector (DSA)

Photo/Heat Detector (PSHA)

Fixed Heat Detector (FHA)

Combination Fixed / ROR Heat

Detector (RHA)

Conv. Zone Module (CIZM)

Mini Contact Mod (MCM)

Single Contact Mod (SCM)

Dual Contact Mod (DCM)

Mon. Output Mod (MOM)

Twin Relay Module (TRM)

Sounder Base (ASB)

Relay Base (ARB)

All settings allowed

Specifies use/type of

SLC device

SLC Point

Dry Contact Input

Functions

Y

Pull Station, Water Flow,

Supervisory, Tamper, Fire Drill,

Trouble Monitor, Aux, Abort,

Reset, Silence, Fire Alarm,

Disable Inputs, Disable Outputs,

Disable Inputs/Outputs, Lamp

Test

All settings allowed

Applies to all dry-

contact input devices

and circuits.

SLC Point

Alarm Verif

Y

Yes/No

All settings allowed

SLC Point

Supervisory

Y

Yes/No

All settings allowed

NACs

Function

Potter/Amseco Sync

Gentex Sync

System Sensor Sync

Wheelock Sync

Constant Output

Resettable Output

Door Holder Output

ANSI Output

City Tie Output

Release / Solenoid Output

All settings allowed

Specifies use of

NAC circuit(s)

Day/Night

Smoke Sensitivity

Y

Full listed range of

smoke detector

All settings allowed

Up to 50 holidays where

day mode is not active.

DACT

Daily Test Call

Y

Any time of day

All settings allowed

Alternates between line

1 and 2 if line 2

is enabled.

E-Mail

E-mail Status

Reports

N

Alarms, Troubles, Supervisory

Test, History & Status Reports

IP-Dialer

IP Based Central

Station Reporting

Y

Alarms, Supervisory,

Trouble & Test Reports

All settings allowed