Potter PFC-6075R User Manual

Page 29

Advertising
background image

3-23

PFC-6075R • 5403594 • REV D • 9/14

For a Single Device:
1. From the SLC Addr Prog menu, press 1 to address a Single device.
2. Attach connector wires to SLC PGM terminals, if not already done. The “Connect Device” prompt displays.
3. Connect device. The “Found Address: xx” prompt displays.

y

y

Modify new address, if needed, or press ENTER to continue.

y

y

TheWriting Addr: XX” prompt displays, and the system beeps three (3) times when completed.

When addressing is completed, the “Found Addr: XX, New Addr: XX” prompt displays.

y

y

Disconnect device, and continue with next device.

y

y

Repeat steps, as needed.

4. Press ESC when finished.

For Multiple Devices:
1. From the SLC Addr Prog menu, press 2 to address Mult device.

•y

The “Start Address: XX” prompt displays.

•y

Modify starting address, if needed, and press ENTER.

•y

The prompt “Connect Device” displays.

2. Connect 1

st

device. The “Addr = XX Next = XX Remove” prompt displays.

•y

Disconnect the device, connect next device. Addressing is completed when the panel emits a series of three (3) beeps.

•y

The “Addr = XX Next = XX Remove” prompt displays.

•y

Continue with next device, following prompts.

Notes:

•y

The prompt Addr = XX” refers to the current device number, and “Next = XX” is the next sequential address number.

•y

When configuring a Class B DCM-4, press the UP ARROW to skip the next sequential number. The Class B DCM-4

requires 2 addresses; if this isn't done, the next available address will be assigned to a different device and the DCM-4

will operate as a single point device.

3. Press ESC when finished.