5-47

PFC-6075R • 5403594 • REV D • 9/14

Section 5: Programming

This section addresses programming options and their parameters, provides an overview of the programming process, and

addresses how to use the two programming methods: (1) the LEARN function, and (2) the remote computer programming

process.
This section also includes procedures on uploading and downloading configuration data using the panel configuration software.

Please refer to this section to learn how to navigate within the software, access and modify programming settings, such as the

system clock and day/night mode sensitivity settings, scheduling holidays, displaying events, and programming optional modules

(i.e., a DACT, remote and LED annunciators, and a Class A card).

Programming Options

Table 9: Programming Options

Topic

Feature or

Option

Permitted

in UL (Y/N)

Possible Settings

Setting(s) Permitted

in UL864?

Comment

Misc

Idle LCD

Message

Y

Yes/No

All settings allowed

Misc

Display Events

Y

Initial Event

Newest Event

Initial Event

Auto display of

first event

Misc

SLC Blink

Y

Normal/Slow/Off

All settings allowed

Misc

Alarm

Verification Time

Y

0-60 Sec

All settings allowed

Misc

Waterflow Delay

Y

0-255 Sec

0-90 sec

Misc

AC Report Delay

Y

0-30 Hours

1-3 Hours

For UL864 use 1-3 Hr

Misc

DH Low AC

Dropout Delay

Y

No delay, 15 sec, 1 minute,

5 minute

All settings allowed

Misc

Auto Test Time

Y

Time of Day

All settings allowed

Misc

Strobes Active

When Silenced

Y

Yes/No

All settings allowed

Misc

50 Hz AC

Y

Yes/No

All settings allowed

Misc

Display AM/PM

Y

AM/PM, 24 Hour

All settings allowed

Misc

Time Zone

Y

24 Time Zone Selections

All settings allowed

Misc

DST Enabled

Y

Yes/No

All settings allowed

Misc

DST Start

Y

Month/Day

All settings allowed

Misc

DST End

Y

Month/Day

All settings allowed

To users, installers, authorities having jurisdiction, and other involved

parties:

This product incorporates field-programmable software. In order for the

product to comply with the requirements in the Standard for Control Units

and Accessories for Fire Alarm Systems, UL 864, certain programming

features or options must be limited to specific values or not used at all as

indicated below.

Advertising