Connecting analog detectors, Connecting addressable modules – Potter PFC-6075R User Manual

Page 23

Advertising
background image

3-17

PFC-6075R • 5403594 • REV D • 9/14

From FACP or the previous

addressable device on the SLC loop

To the next addressable device

S+

S+

S-

S-

DWG #593-10

Connecting Analog Detectors

When installing analog detectors, such as a photoelectric smoke sensor (PSA), photo smoke/fixed heat detector (PSHA), heat

detector (FHA), or an analog combination type heat detector (RHA), use detector bases (i.e. AB-6). An analog detector activates

its response LED when activated. An example of wiring an analog detector is shown below.

Figure 10. Analog Detector Wiring Example

Connecting Addressable Modules

This section provides examples of wiring addressable modules, including Conventional Initiating Zones (CIZM-4), Miniature

Contact (MCM), Single Contact (SCM-4), Dual Contact Module (DCM-4), Twin Relay (TRM-4), Monitored Output (MOM-4),

Analog Relay (ARB), Analog Sounder Base (ASB), and Addressable Pull Station (APS) modules.

Conventional Initiating Zones (CIZM-4) Class A

Figure 11. CIZM-4, Class A

Note: The resistance of external wiring shall be less that 100Ω.

The capacitance of external wiring shall be less than 1 micro farads.

From FACP or

Previous Module

To Next Module

From FACP

or Previous Module

To Next

Module

24-

24+

S-

S+

SLC Loop

LED

JP1

Select Style D

Conventional

Detector

_

+

_

+

_

+

Conventional Initiating Zone Module

Model No. CIZM-4

A-

A+

B-

B+

DWG #593-11

Notes:

1. The resistance of external wiring shall be less than 100 ohms.

2. The capacitance of external wiring shall be less than 1 micro F.

3. In this style, the open circuit “trouble condition” of IDC is latched at the control panel until system is reset.

Therefore, the system MUST be reset at the control panel after clearing the open circuit condition at the site.

4. Refer to the CIZM data sheet for information on compatible devices.

Conventional Initiating Zones (CIZM-4) Class B

Figure 12. CIZM-4, Class B

Conventional Initiating Zone Module

Model No. CIZM-4

Note: The resistance of external wiring shall be less that 100Ω.

The capacitance of external wiring shall be less than 1 micro farads.

From FACP or

Previous Module

To Next Module

From FACP or

Previous Module

To Next Module

24-

24+

S-

S+

A-

A+

SLC Loop

LED

JP1

Conventional

Detector

5.1KΩ 1/2W

EOLR

_

+

_

+

_

+

B-

B+

Select Style B

DWG #593-12