Delta RMC151 User Manual

Page 210

Advertising
background image

RMC70/150 and RMCTools User Manual

5. The value obtained from the SSI data is put in the Raw Counts register for that axis.

The Raw Counts are converted to Counts and then into an Actual Position in user-

defined units.

SSI Cable Length

The maximum allowable SSI cable length depends on the SSI Clock Rate. For SSI inputs

on the UI/O module, wire delay compensation is available to allow longer lengths, as

described in the Wire Delay Compensation section below.

Clock Rate

Maximum Cable

Length*

100 kHz

2100 ft (640 m)

150 kHz

1360 ft (415 m)

230 kHz

850 ft (255 m)

250 kHz

770 ft (235 m)

375 kHz

475 ft (145 m)

500 kHz

325 ft (99 m)

921 kHz

120 ft (37 m)

971 kHz

110 ft (34 m)

* The cable lengths are approximate, and may be affected by the type of wire and

transducer.

Wire Delay Compensation (UI/O Module Only)

Wire delay compensation is available on the RMC150 Universal I/O Module and is required

for SSI wire runs that exceed the lengths given in the SSI Cable Length section above.

If the wire to the SSI device is very long, there will be a significant delay between the

clock signal and the returned data signal. As shown in the diagrams below, if this delay

exceeds one clock period, the RMC will not receive the correct data, unless the SSI Wire

Delay parameter is used.
Minimal Delay
The timing diagram below shows an SSI system with very little delay. On the first rising

edge of the Clock, the SSI device puts the first bit of data on the Data line. By the next

rising edge of the Clock, when the RMC samples the data, the data is valid, and the read

is successful.

Excessive Delay
The timing diagram below shows an SSI system with a time delay of more then one clock

period. On the first rising edge of the Clock, the SSI device puts the first bit of data on

the Data line. By the next rising edge of the Clock, when the RMC samples the data, the

data from the SSI device has not yet arrived, and the SSI input will not return the correct

value.