Using a profinet i/o connection, E using a profinet i/o connection, Selecting the input and output modules – Delta RMC151 User Manual

Page 491: E using, A profinet i/o connection

Advertising
background image

6 Communication

recommended because it can result in the IP address being changed or cleared at times

when RMCTools is connected to the RMC.
An alternative method is to set the IP address settings in RMCTools, and then instruct the

IO-Controller through the PROFINET Configuration Software to leave the IP address as it

is when connecting to the IO-Device. For example, STEP7’s HW Config software version

5.5 includes an Assign IP address via IO controller checkbox in the IO device’s

general properties that should be unchecked to choose this option. This is the

recommended method for RMC controllers.
Selecting the Input and Output Modules
The RMC PROFINET devices are set up to have 3 virtual slots. The first slot is the DAP,

and will be named RMC150E or RMC75E. The second slot is the Input Slot, and the third

slot is the Output Slot. In the PROFINET IO device library, under the selected DAP, you

will find a folder of input modules and a folder of output modules. Select exactly one

Input module and one Output module to install in slots 1 and 2 respectively.
The Input and Output modules to choose from differ only in the number of registers to be

transferred. The Input module corresponds to the Outgoing Cyclic I/O Data area in the

RMC, and the Output module corresponds to the Incoming Cyclic I/O Data area. Notice

that if the Sync Register is used, the first register in each block will be reserved as the

Sync Register.
Setting the Update Time
One additional item configured in the PROFINET configuration software that affects the

PROFINET communication with the RMC is the Update Time. The RMC75E and RMC150E

controllers support update times of 2 ms, 4 ms, 8 ms, 16 ms, 32 ms, 64 ms, 128 ms, 256

ms, and 256 ms. Notice that the update time cannot be set lower than the Loop Time of

the RMC. Therefore, if a 4 ms loop time is used, then the minimum PROFINET update

time will be 4 ms.
Related to the Update Time is the Watchdog Time. This is specified as a multiple of the

Update Time. For example, with a Watchdog Time multiplier of 3 and an Update Time of

16 ms, the Watchdog Time will be 48 ms. Most IO controllers fix this value at 3, but some

may allow configuration of this value.

6.8.10.7.3. Using a PROFINET I/O Connection

This topic describes the how to control the RMC via the PROFINET I/O connection's cyclic data.

For detail using the acyclic data, see Using PROFINET Record Data. For details on setting up a

connection, see the Setting up a PROFINET I/O Connection topic.

Understanding the Sync Register

The cyclic I/O data can operate in two modes: with a Sync Register and without a Sync

Register. When using a Sync Register, the first Input Data register and first Output Data

register are each reserved as a Sync Register, and the RMC processes incoming data only

when the Sync Register changes. When not using a Sync Register, the RMC processes

incoming data each time any register in the block changes.
The Sync Registers show up in the Input and Output Data images in the PLC. In the RMC,

they are only visible in the Event Log. See Troubleshooting PROFINET for details.
Why Use a Sync Register?
The Sync Register gives the user tight control over synchronization between the PLC and

RMC. In applications that do not require this level of synchronization, the user can choose

to not include the Sync Register.
The synchronization provided by the Sync Register is useful when:

Treating writes to a block of registers as a consistent block.

Not all PLCs synchronize their I/O with the PLC scan. Therefore, while data is being placed

deltamotion.com

471

Advertising
This manual is related to the following products: