8 Command Reference

In this example, Axis 1 (slave) gears to Axis 0 (master) at a 1:1 ratio. Both axes start at

0 pu. The master starts moving at time 0. At 0.2 seconds, the following Gear Pos (Clutch

by Time) command is issued to the slave.

Numerator = 1
Denominator = 1
Master Register = _Axis[0].TarPos
Clutch Time = 0.2 sec

The plot below shows how the slave moves.

Legend:

Master Position

— Master Velocity

Slave Position

— Slave Velocity

At 0.2 seconds, when the command was issued to the slave, it began ramping up the

velocity such that slave reached the specified gear ratio at 0.4 seconds.
Applications Not Suitable for Clutch by Time
The Gear Position command clutches based on time, which means it will reach the

requested gear ratio in the time specified. This command is not well-suited for the

following types of applications:

If Position at which Axis Reaches Gear Ratio is Important

The Gear Pos (Clutch by Time) command does not directly specify the position at

which the gear ratio will be reached. If the axis must reach the requested gear ratio at

a certain position, such as in flying cut-off applications, use the Gear Pos (Clutch by

Distance) (32) command instead.

If Maximum Velocity or Acceleration Must be Specified

The Gear Pos (Clutch by Time) command does not limit the velocity or acceleration. If

you need to limit the velocity or acceleration, use the Gear Pos (Clutch by Rate) (39)

instead.

Specifying a Register Address

When issuing this command from anywhere other than RMCTools, the addresses in the

Master Register command parameter must be entered as an integer value.
RMC addresses are represented in IEC format as:

%MDfile.element, where file = file number, and element = element number.

Use the following equation to convert a register address to integer format, N:

N = file * 4096 + element