CIRCUTOR CVMk2 Series User Manual

Page 145

Advertising
background image

145

CVM

k2

CHARACTERISTICS

Output range points

4.000

COMMUNICATIONS

Network protocol

RS-485

Communication protocol

Modbus/RTU

Speed (configurable)

9600, 19200, 38400, 57600 baud

Parity

even, odd or no parity

Stop bits

1 or 2

ETHERNET OUTPUT

Network protocol

RJ-45 ETHERNET

Communication protocol

Modbus/TCP

Speed

10baseT / 100baseTx compatible

ENVIRONMENT

Operating temperature

- 10…+ 40 °C

Storage temperature

- 20… + 65ºC

Relative Humidity

95% with no condensation

Facility category

CAT III in accordance with CEI 61010

Degree of contamination

2 in accordance with IEC 61010

Protection index

IP51 front - IP20 rear

For use on a Flat Surface of a Type 1 Enclosure (only for the display module)

MECHANICAL

Connection

Terminal board with screws for rigid 2.5 mm (4.5 mm

2

) or

flexible wires (AWG 11)

Field Wiring terminals to use Copper Conductors only, wire size AWG 14, minimum temperature rating 60º

STANDARDS

EMC

61000-4-2, 61000-4-3, 61000-4-11, 61000-4-4, 61000-4-5

Listed for industrial control equipment miscellaneous

device.

FILE: NMTR E227534

MODEL 405 ACCURACY

( % MEASURE ) ± ( DIGIT )

Currents

± 0,5% ± 1 from 10% to 120% of In

Neutral current

± 0,5% ± 1 from 10% to 120% of In

Voltages

± 0,5% ± 1 from 20% to 120% of Un

Active Power P

± 0,5% ± 1 from 10% to 120% of In

Reactive Power Q

± 0,5% from 10% to 120% of In

Apparent Power S

± 0,5% from 10% to 120% of In

Frecuency

± 0,01 Hz from 45 to 65 Hz

Active Energy

± 0,5%

Reactive Energy

± 0,5%

MODEL 402 ACCURACY

( % MEASURE ) ± ( DIGIT )

Currents

± 0,2% ± 2 from 10% to 120% of In

Neutral current

± 0,5% ± 1 from 10% to 120% of In

Voltages

± 0,2% ± 2 from 20% to 120% of Un

Active Power P

± 0,2% ± 1 from 10 % to 120% of In

Reactive Power Q

± 0,5% from 10% al 120% of In

Apparent Power S

± 0,5% from 10% al 120% of In

Frecuency

± 0,01 Hz from 45 to 65 Hz

Active Energy

± 0,2%

Reactive Energy

± 0,5%