Expansion card parameters, Features – CIRCUTOR CVMk2 Series User Manual

Page 59

Advertising
background image

59

CVM

k2

CONFIGURA

TION

FEATURES

VALUE

UNIT

ANALOGUE OUTPUTS

Maximum internal voltage

12

VDC

Maximum external voltage

24

VDC

Rated output range

0/4 ... 20

mA d.c

Linearity

1

%

Load resistance range

< 300

Ω

Load resistance range (external supply)

< 600

Ω

Resolution

4.000

points

ANALOGUE INPUTS

Type of measurement

Current

Rated input range

0/4 ... 20 mA

mA d.c

Measurement precision

1

%

Input impedance

200

Ω

CONNECTIONS

Wire cross section (Cu)

0,05..1 (AWG 30...18)

mm

2

Maximum torque

0,3

Nm

MECHANICAL

Terminals protection

IP 20

4.7.3.5. Features

4.7.3.4. Expansion card parameters

To see the parameters of the expansion card, you have to intro in

menu

, select

cards

, and go

to the card to see the parameters.

The picture shows the status of the inputs of the cards or the number of impulses that has

configured each one.