4 system connection, 1 auxiliary power supply, 2 rated voltage in voltage measuring circuit – CIRCUTOR CVMk2 Series User Manual

Page 18: 3 rated current in current measuring circuit, 4 working conditions

Advertising
background image

18

CVM

k2

INST

ALLA

TION

2.4 SYSTEM CONNECTION

Before connecting the equipment, the following points should be verified:

2.3.1 Auxiliary Power Supply Features

2.3.2 Maximum Voltage in the Voltage Measuring Circuit

2.3.3 Maximum Current in the Current Measuring Circuit

2.3.4 Working Conditions

2.3.5 Safety

Standard rated voltage (*)

300 / 520

V

f-n

/ V

f-f

Other voltages (*)

500 / 866

V

f-n

/ V

f-f

(*) Current limited. Máximum 0.6 V·A

Rated frequency

45,00...65,00

Hz

U

max

= U

N

x 1.2

Secondaries .../5A (*)

5

A a.c.

Secondaries .../1A (*)

1

A a.c.

(*) limited in voltage

I

max

= I

N

x 1.2

2.4.3 RATED CURRENT IN CURRENT MEASURING CIRCUIT

Operating temperature

-10...+40

ºC

Relative Humidity

5...95

%

2.4.4 WORKING CONDITIONS

2.4.2 RATED VOLTAGE IN VOLTAGE MEASURING CIRCUIT

Standard power supply

85...265

100...300

V a.c.

V d.c.

Frequency

50...60

Hz

Optional power supply

24...90

V d.c.

2.4.1 AUXILIARY POWER SUPPLY