----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 11

4.3.3.- Module for residual and neutral currents (770 572, 770 575 and 770578)

Description

Lable in the expansion module connection terminal

Mod CVM 144 -C2-Currents

(Code: 7 70 572)

13

14

15

16

17

18

19

20

21

22

23

24

250 V

3 A

RL1

RL2

I

N

Mod CVM 144 RS485-C2-Currents

(Code: 7 70 575)

13

14

15

16

17

18

19

20

21

22

23

24

250 V

3 A

R

S 485

(+)

(-)

G

N

D

RL1

RL2

I

N

Mod CVM 144 RS232-C2-Currents

(Code: 7 70 578)

13

14

15

16

17

18

19

20

21

22

23

24

250 V

3 A

RL1

RL2

I

N

Mod CVM 144

C2-Currents

(Code: 7 70 572)

Mod CVM 144

RS485-C2-Currents

(Code: 7 70 575)

Mod CVM 144

RS232-C2-Currents

(Code: 7 70 578)

Nº Terminal description

Nº Terminal description

Nº Terminal description

13
14

15

16
17
18
19
20
21
22
23
24

Measur. residual current S1
Measur. residual current S2

(30 A)

Measur. residual current S2

(3 A)

Measur. neutral current S1
Measur. neutral current S2
Not used
Not used
Not used
Relay RL2 output
Relay RL2 common
Relay RL1 output
Relay RL1 common

13

14

15

16
17
18
19
20
21
22
23
24

Measur. residual current S1
Measur. residual current S2

(30 A)

Measur. residual current S2

(3 A)

Measur. neutral current S1
Measur. neutral current S2
RS-485 ( GND )
RS-485 ( - )

RS-485 ( + )
Relay RL2 output
Relay RL2 common
Relay RL1 output
Relay RL1 common

13
14

15

16
17
18
19
20
21
22
23
24

Measur. residual current S1
Measur. residual current S2

(30 A)

Measur. residual current S2

(3 A)

Measur. neutral current S1
Measur. neutral current S2
RS-232 ( GND )
RS-232 ( Rx )

RS-232 ( Tx )
Relay RL2 output
Relay RL2 common
Relay RL1 output
Relay RL1 common

Notes:

For the measurement of the residual current (earth leakage current), the use of

transformers of the WG xx series is required. These transformers can be connected
to the 3 A or 30 A rated input, depending on the needed measuring range.

For the measurement of the neutral current, the use of .../5A current transformers is

required.