EXAMPLE

INQUIRY

0A 04 00 00 00 0A 71 76

0A

CVM-144 peripheral number, 10 in decimal

04

Reading function

00 00

Initial address (first register)

00 0A

Number of registers to be read

7176

CRC character

ANSWER

0A 04 14 00 00 08 4D 00 00 23 28 00 00 0F A0 00 00 00
90 00 00 00 60 CB 2E

0A

CVM-144 number , 10 in decimal

04

Reading function – the one use for the inquiry

14

Bytes received (20)

00 00 08 4D

V 1x10 (register 00 Hex), in decimal 212.5 V

00 00 23 28

mA 1, in decimal 9000 mA

00 00 0F A0

W 1, in decimal 4000 W

00 00 00 90

varL 1, in decimal 144 varL

00 00 00 60

PF 1 x 100, in decimal 96 PF

CB 2E

CRC character