CIRCUTOR CVM144 Series User Manual

Page 49

Advertising
background image

----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 48

11.4.- MODBUS © protocol

The CVM-144 analyzer can communicate by means of the MODBUS ©

protocol, as it is following described:

When the CVM-144 communicates with MODBUS protocol, it uses the RTU

mode (Remote Terminal Unit ). Each 8-bits byte in a message contains two 4-bits
hexadecimal characters.

The format for each byte in RTU mode is :

* Code :

8-bits binary, hexadecimal 0-9, A-F

Two hexadecimal characters

contained in each 8-bits field of the
message.
* Bits per Byte

:

8 data bits

* Error Check Field

:

Cyclical Redundancy Check ( CRC ) .


MODBUS FUNCTIONS:

FUNCTION 01

Reading of relay state

FUNCTION 3 or 4

Reading of n Words (16 bits-2 bytes). This function
permits to read all the electrical parameters of the
CVM-144. Each parameters is a 32-bits long, hence
two words are required to inquiry for a parameter.

FUNCTION 05 Writing one relay

Advertising