----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 37

6.12.- Additional screens with 4 - 20 mA outputs y inputs

CVM-144 equipped with an “Analogue” type module provides 4 - 20 mA d.c.

or 0 - 20 mA d.c. inputs and outputs (inputs can also optionally be 0-10 V type).

6.12.1.- Additional screen with the 4 - 20 mA output

These can be programmed to obtain an output signal proportional to any of

the parameters measured by the CVM-144, including the ability of setting the
scale (offset and full-scale values).

On the CVM screen following messages appear at this SET-UP point

(provided the right module is connected to the equipment):

a.- Parameter choosing:

dA 1

OUTPUT D/A Nr.1

Code

xx

Parameter No.

- "max" -- "min" keys: permits the user to choose any parameter measured by the

CVM-144 but the parameters referred to energies..

- "display" key: validates the selected option and passes to the next setup screen.

b.- Election of 0 - 20 mA or 4 - 20 mA :

dA 1

OUTPUT D/A Nr.1

Scal

Scale :

4 - 20

allows choosing a 0 - 20 mA

or 4 - 20 output ("max" or "min" key)

- "display": to validate the selected option and pass to the next setup screen.

Advertising