CIRCUTOR CVM144 Series User Manual

Page 54

Advertising
background image

----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 53

b.- Reading of digital inputs and outputs

Inquiry

Relay outputs

Digital inputs

Answer

PP0100000008 CRC

PP0100100004 CRC

PP0101XXCRC

Where:PP peripheral No.

XX (hexadecimal byte) translated to binary

b7 b6 b5 b4 b3 b2 b1 b0

bit

Relay outputs

Digital inputs
(

770 579 y 770 580)

bo

relay 1

Digital input 1

b1

relay 2

Digital input 2

b2

No used

Digital input 3

b3

No used

Digital input 4

c.- Write of digital outputs

This function is used to force the status of the CVM-144 digital outputs.

Output No.

Message

Answer

Relay 1
Relay 2

PP050000xx00 CRC
PP050001xx00 CRC

PP050000xx00 CRC
PP050001xx00 CRC

Where: PP peripheral No.

xx 00 Deactivate
FF Activate

Advertising