----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 49

a.- Registers assigned to different parameters measured by the CVM-144:

MODBUS REGISTERS

HEXA-DECIMAL

(longs)

PARAMETER

Units

PRESENT

Value

MAXIMUM

Value

MINIMUM

Value

Phase voltage - V 1

V x 10

00-01

60-61

C0-C1

Current - A 1

mA

02-03

62-63

C2-C3

Active power - kW1

W

04-05

64-65

C4-C5

Reactive power - kvar 1

var

06-07

66-67

C6-C7

Power factor - PF1

PF x 100

08-09

68-69

C8-C9

Phase voltage - V 2

V x 10

0A-0B

6A-6B

CA-CB

Current - A 2

mA

0C-0D

6C-6D

CC-CD

Active power - kW2

W

0E-0F

6E-6F

CE-CF

Reactive power - kvar 2

var

10-11

70-71

D0-D1

Power factor - PF2

PF x 100

12-13

72-73

D2-D3

Phase voltage - V 3

V x 10

14-15

74-75

D4-D5

Current - A 3

mA

16-17

76-77

D6-D7

Active power - kW3

W

18-19

78-79

D8-D9

Reactive power - kvar 3

var

1A-1B

7A-7B

DA-DB

Power factor - PF3

PF x 100

1C-1D

7C-7D

DC-DD

Three-phase active power-kWIII

W

1E-1F

7E-7F

DE-DF

Three-phase inductive power-kvarL III

var

20-21

80-81

E0-E1

Three-phase capacitive power-kvarC III

var

22-23

82-83

E2-E3

Cos

ϕ

III

Cos

ϕ

x100

24-25 84-85 E4-E5

Three-phase power factor - PF III

P.F.x100

26-27

86-87

E6-E7