----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 30

6.11.- Additional screens when RELAY OUTPUTS (2 relays) are equipped

With these outputs the CVM-144...C2 can be set to deliver:

A.- Pulse every certain kWh or kvarh (ENERGY). You can define the

value corresponding to the energy consumed for generating a pulse (0.5 s long):
kWh / 1 pulse or kvarh / 1 pulse

B.- ALARM conditions: the parameter to be controlled, the maximum value,

the minimum value and the delay are user-definable for each relay output.

----------------------------------------------------------------------------------

On the CVM-144 screen following messages appear at this SET-UP option:

OUT 1

RELAY 1

CODE

00

Parameter No. (1)

Depending on the selected variable we will pass to a.- or b.- sections

In case that no parameter is wanted to be programmed set par. No. = 00.

Parameter

Symbol

phase L1

Code

Symbol

phase L2

Code

Symbol

phase L3

Code

Single voltage

V 1

01

V 2

06

V 3

11

Current

A 1

02

A 2

07

A 3

12

Active power

kW 1

03

kW 2

08

kW 3

13

Reactive power
Inductive/ Capacitive

kvarL 1

kvarC 1

04 kvarL

2

kvarC 2

09 kvarL

3

kvarC 3

14

Power factor

PF 1

05

PF 2

10

PF 3

15

% THD V

THD V1

25

THD V2

26

THD V3

27

% THD A

THD A1

28

THD A2

29

THD A3

30