----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 51

MODBUS REGISTERS

HEXA-DECIMAL

(longs)

PARAMETER

Units

L1

L2

L3

Fundamental mA

1F4-1F5

212-213

230-231

Harmonic 2

%

1F6-1F7 214-215

232-233

Harmonic 3

%

1F8-1F9 216-217

234-235

Harmonic 4

%

1FA-1FB 218-219

236-237

Harmonic 5

%

1FC-1FD 21A-21B

238-239

Harmonic 6

%

1FE-1FF 21C-21D

23A-23B

Harmonic 7

%

200-201 21E-21F

23C-23D

Harmonic 8

%

202-203 220-221

23E-23F

Harmonic 9

%

204-205 222-223

240-241

Harmonic 10

%

206-207 224-225

242-243

Harmonic 11

%

208-209 226-227

244-245

Harmonic 12

%

20A-20B 228-229

246-247

Harmonic 13

%

20C-20D 22A-22B

248-249

Harmonic 14

%

20E-20F 22C-22D

24A-24B

Harmonic 15

%

210-211 22E-22F

24C-24D

NOTE: The maximum number of parameters (1 parameter = 1 word of 32 bits) that can be

read in one transmission is 20.