CIRCUTOR CVM144 Series User Manual

Page 56

Advertising
background image

----- Supply network analyzer CVM-144 ------ User's manual --- Page No. 55

b.- SETTING COMMUNICATION PARAMETERS

SET

Cdef

Default configuration

NO

"max" key to switch from NO / YES

If YES is chosen: the configuration is 001 / 9600 / 8 bits / N / 1 bit

If NO is chosen, pressing "

" following options successively appear:

- n PER

:

Peripheral No. 001 to 255

- Baud 1

:

baud rate 1.200 – 2.400 – 4.800 – 9.600 – 19.200

- Parity

:

No, even, odd

- LEN

:

(length) 8 bits

- Stop bits

:

1 or 2

12.2.- SET-UP locking or unlocking

SET

Up

Unlo

Loc (locked SET-UP) or Unloc (unlocked SET-UP)

Use the key "max" to modify the choice.

- Whether LOC is set, when the SET-UP is accessed, configuration

parameters can be visualized but cannot be modified.

- To modify the previously set option, a 4-figure password is required to be

entered (in case that this password is not correct, this blinks and the previous
menu is again accessed).

PASSWORD : 1234

To exit this set-up mode, the key RESET can be pressed at any moment

(WARNING: if the set-up is exited by pressing the key RESET some last
modifications might not be saved in memory) or reach the end of this set-up mode.