Series f-1200 dual turbine flow meters, General practices, 2 insertion meter straight run requirements – ONICON F-1100 Series User Manual

Page 10

Advertising
background image

11451 Belcher Road South, Largo FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
Turbine Flow Meter Manual 05/14 - 0721-3 / 13518

Page 10

FLOW DIRECTION

STRAIGHT RUN REQUIREMENTS FOR INSERTION TURBINE FLOW METERS

Series F-1100 Single Turbine Flow Meters

GENERAL PRACTICES

1. For best results, install the flow meter in a straight run of pipe,

free of bends, tees, valves, transitions, and obstructions for a

distance of at least 20 pipe diameters upstream and 5 diameters

downstream.

2. Longer straight runs may be required in applications where the

meter is placed downstream from devices which cause unusual

flow profile disruption or swirl, for example, modulating valves or

two elbows in close proximity and out of plane, etc.

3. If there is not sufficient straight run, allow 80% of the run upstream and

20% of the run downstream. If the total length of straight run is less

than 20 diameters, performance may seriously

degrade, and consideration should be given to

changing to the series F-1200 Dual Turbine

Flow Meter.

FLOW DIRECTION

Minimum upstream

straight run distance

20 pipe diameters from any

valve, elbow, fitting, etc.

Minimum downstream

straight run distance

5 pipe diameters to any

valve, elbow, fitting, etc.

Series F-1200 Dual Turbine Flow Meters

FLOW DIRECTION

GENERAL PRACTICES

1. For best results, install the flow meter in a straight run of pipe,

free of bends, tees, valves, transitions, and obstructions for a

distance of 10 pipe diameters upstream and 5 diameters

downstream.

2. Longer straight runs may be required in applications where the

meter is placed downstream from devices which cause unusual

flow profile disruption or swirl, for example, modulating valves or

two elbows in close proximity and out of plane, etc.

3. If there is not sufficient straight run, allow 80% of the run upstream and

20% of the run downstream. If the total length of straight run is less

than 70% of recommended distance, performance

may degrade and consideration should be given to

changing to the F-3000 Series Inline

Electromagnetic flow meter.

FLOW DIRECTION

Minimum upstream

straight run distance

10 pipe diameters from any

valve, elbow, fitting, etc.

Minimum downstream

straight run distance

5 pipe diameters to any

valve, elbow, fitting, etc.

3.2 INSERTION METER STRAIGHT RUN REQUIREMENTS