Wiring information, Flow meter wiring information, Fb-1211 wiring diagram – ONICON F-1100 Series User Manual

Page 34: Caution

Advertising
background image

11451 Belcher Road South, Largo FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
Turbine Flow Meter Manual 05/14 - 0721-3 / 13518

Page A-6

8-20-01

0273

1500 North Belcher Road, Clearwater, Florida 33765 Tel (727) 447-6140 Fax (727) 442-5699

www.onicon.com E-mail: [email protected]

FLOW METER WIRING INFORMATION

User Connections for Models with Isolated Analog Outputs
Models: F-1111, F-1211, FB-1211 & F-1311

Wiring Information

WIRE COLOR CODE

NOTES

(+) 24 ± 4 V AC/DC
supply voltage

RED

*

BLACK

(–) Common ground
(Common with pipe ground)

Connect to power supply
negative

GREEN

(+) Frequency output signal:
0-15 V peak pulse

Required when meter
is connected to local
display or BTU meter

BLUE

(+) Analog signal:
4-20 mA (isolated)

Both signals may be
used independently
(unless 0-5 V output
is ordered)

BROWN

(+) Analog signal:
0-10 V (isolated)
(Can also be ordered
as 0-5 V)

GRAY

VIOLET

Dry contact directional
output - indicates
flow direction

Contact closed when flow
is in direction of arrow
on meter

DIAGNOSTIC SIGNALS

ORANGE Bottom turbine frequency

WHITE

Top turbine frequency

These signals are for
diagnostic purposes -
connect to local display
or BTU meter

Connect to power supply
positive

F-1111

Single

Turbine

F-1311

Inline

F-1211

Dual

Turbine

FB-1211

Bi-Directional

FB-1211 Wiring Diagram

Connections to a Control System (No Display or BTU Meter)

F-1111 / F-1211 / F-1311 Wiring Diagram

Connections to a Control System (No Display or BTU Meter)

NOTES:

*

1. Serial Numbers 115691 and earlier require 24 VDC. Serial Numbers 115692 and higher

can accept 24 V AC/DC.

2. Black wire is common with the pipe (typically earth ground).

3. For ONICON display module or BTU meter, connect all wires provided. Refer to wiring diagram

provided with display or BTU meter.

4. This is NOT a "loop-powered" instrument. DO NOT connect power to any of the signal

output wires (blue, brown, green, orange or white)

FLOW METER

FLOW METER

RED

BLACK

BLUE

BROWN

YELLOW

GRAY

VIOLET

+ 24 V

COM

Power

Source

OR

ANALOG INPUT

SIGNAL GROUND

Control System

BINARY (DIGITAL) INPUT

(Direction)

RED

BLACK

BLUE

BROWN

YELLOW

+ 24 V

COM

ANALOG SIGNAL INPUT

SIGNAL GROUND

Power

Source

Control System

OR

YELLOW

(–) Isolated ground

Use for analog signals only

0273

CAUTION

This is NOT a “loop-powered” instrument. DO NOT connect power to any of the signal output

wires (blue, brown, green, orange or white)

!

Advertising
This manual is related to the following products: