Turbine Flow Meter Manual 05/14 - 0721-3 / 13518

Page B-2

11451 South Belcher Road, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699

www.onicon.com • [email protected]

04-14

0536-2 / 15950

Installation Hardware Instructions
Standard Installation Kit for Welded Steel Pipe

For F-1100, F-1200 & FB-1200 Series Insertion Turbine Flow Meters

IMPORTANT NOTE

ONICON insertion flow meters are

precision measuring devices that

must be installed according to the

instructions contained in this

document in order to maintain their

accuracy and reliability. Failure to

follow these instructions will result

in erratic operation and reduced

accuracy.

This kit must be installed prior to filling the system, or into a section of pipe that is isolated from

pressure and flow. Once installed, this kit allows for insertion and removal of the flow meter without

a system shutdown.

Do not substitute threaded tees for

the welded branch outlet. Contact

ONICON if you need installation

hardware for threaded pipe.

For Use With Kits: INSTL1, INSTL5, INSTL18

Directions:

1. Identify an appropriate location for the flow

meter (see pages 2-4).

2. Weld the branch outlet onto the pipe.

3. Drill a one inch (minimum) access hole,

centered in the branch outlet.

4. Install the close nipple and ball valve as

shown below. Use a paste type thread

sealant. DO NOT use Teflon

®

tape.

5. Flush and fill the system prior to installing the

flow meter.

NOTE: Before installing the flow meter, read the entire installation manual.

(see Sections 3.1 and 3.2).