1.3 STANDARD FEATURES AND SPECIFICATIONS

(Refer to specification sheet for particular model
to obtain additional details)

ACCURACY

F-1100 / F-1200 / FB-1200 Series
± 0.5% OF READING at calibrated velocity
± 1% OF READING from 3 to 30 ft/s (10:1 range)
± 2% OF READING from 0.4 to 20 ft/s (50:1 range)
F-1300 Series
± 0.5% OF READING at calibrated velocity
± 2% of reading from 0.8 to 38 GPM (50:1 range)
Sensing Method
F-1100 / F-1300 Series

Single turbine electronic impedance sensing
(non-magnetic and non-photoelectric)

F-1200 / FB-1200 Series

Dual turbine electronic impedance sensing
(non-magnetic and non-photoelectric) and
frequency averaging circuitry.

Pipe Size Range
F-1100 Series

1¼” through 72” nominal

F-1200 / FB-1200 Series

2½” through 72” nominal

F-1300 Series

¾” or 1” NPT threaded or copper sweat process
connections

Supply Voltage

24±4 V AC/DC at 50 mA

Liquid Temperature Range

Standard: 140° F continuous, 150° F peak
High Temp: 280° F continuous, 300° F peak
Insertion meters operating above 250° F require
316 stainless steel construction option

Ambient Temperature Range

-5 to 160° F (-20 to 70° C)

Operating Pressure

400 PSI maximum

Pressure Drop
F-1100 / F-1200 / FB-1200 Series

Less than 1 PSI at 20 ft/s in 2½” pipe, decreasing
in larger pipes and lower velocities

F-1300 Series

3 PSI at maximum flow rate

Material

Wetted metal components

F-1100 / F-1200 / FB-1200 Series

Standard: Electroless nickel plated brass
Optional: 316 stainless steel

F-1300 Series

Brass sensor body

Electronics Enclosure
Standard: Weathertight aluminum enclosure
(NEMA4)
Optional: Submersible enclosure (NEMA6)
Electrical Connections
Standard: 10’ of PVC jacketed cable with ½”
NPT conduit connection
Optional: Indoor DIN connector with 10’ of
plenum rated cable
Output Signal(s)
F-1100 / F-1200 / F-1300 Series
Standard: Calibrated frequency output
(0-15 V pulse, 0-500 Hz)
Optional: Analog and digital outputs also
available, based on model
FB-1200 Series
Standard: Calibrated frequency output
(0-15 V pulse, 0-500 Hz), contact closure
output to report flow direction
Optional: Analog and digital outputs also
available, based on model