3.3.4 Customer Supplied Installation Hardware

There are occasions where circumstances require that the customer provide the

installation hardware or that the flow meter be installed through existing hardware.

In these cases, it is important to confirm that the installation hardware is suitable for use

with the flow meter provided by ONICON before it is installed. The installation must

allow for sufficient overhead clearance to fully extract the meter and a full 1” opening in

the pipe wall is required to clear the sensor head and allow for insertion. Make sure that

your valves and fittings are full port and at least 1” in actual internal diameter.

Installation hardware generally consists of three separate component parts:

CAUTION

In order to provide the flow meter with the correct stem length, ONICON must know the

overall height of the installation hardware as measured from the outside wall of the pipe to

the top of the valve where the meter is installed.

!

CAUTION

Use stainless steel or brass nipple only.

IMPORTANT NOTE

Do not use threaded steel or slip PVC tees to provide the 1” opening in the pipe. Tees of this

type will cause significant errors in the flow measurement.

Some type of

threaded branch

outlet,

An

interconnecting

close nipple,

And a full port

isolation valve.

!