ONICON F-1100 Series User Manual

Page 13

Advertising
background image

11451 Belcher Road South, Largo FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
Turbine Flow Meter Manual 05/14 - 0721-3 / 13518

Page 13

3.3.2 ONICON Standard Installation Hardware Kits

Standard installation hardware kits are designed to be installed on piping systems that

are drained and at atmospheric pressure. The access hole is drilled (1” minimum) prior

to installation of the branch outlet with 1” NPT threads, the close nipple and full port ball

valve. Once the isolation valve is installed, the piping system can be flushed, filled and

pressurized. The flow meter may now be inserted or removed by hand without having to

stop flow or drain the system. Please read all instructions before proceeding with meter

insertion.

3.3.3 ONICON Hot Tap Installation Hardware Kits

ONICON offers an alternative installation hardware kit when it is not practical to relieve

pressure and drain the system. In this case, a 1¼” branch outlet, a close nipple and a 1¼”

full port ball valve are installed first. Then, a hot tap drilling apparatus is used to drill a 1”

diameter hole through the valve. This eliminates the need to stop flow and drain the

pipe. Please read all instructions before proceeding with meter insertion.

3.3.1 Insertion Meter Installation Kits

ONICON offers a wide range of installation hardware kits for commonly used pipe

materials. The kits are specifically designed for ONICON insertion flow meters, and their

use is recommended. Refer to Appendix B of detailed infromation regarding ONICON

installation hardware kits.

The use of ONICON installation hardware kits accomplishes two important objectives.

First, it ensures that the proper hardware is used. Second, it simplifies order processing

by standardizing the dimensions of the installation hardware. ONICON must have an

accurate measurement of the overall height of the installation hardware as measured from

the outside wall of the pipe to the top of the valve in order to determine the correct stem

length when assembling insertion meters in our factory. ONICON documents refer to this

dimension as the stack height.

ONICON installation hardware kits consist of three separate component parts:


Different pipe materials require different branch outlets and may include additional

bushings to properly size the opening.

Some type of

threaded branch

outlet,

An

interconnecting

close nipple,

And a full port

isolation valve.

Advertising
This manual is related to the following products: