Connect the power source to the main unit through the conduit opening located on the

bottom of the main unit. Fasten the power wires to the appropriate screw terminals as

shown. Do not exceed 13 in-lb (1.5 Nm) of torque when tightening.

As power is initially applied to the System-10, immediately confirm that the display is
illuminated and scrolling through the character diagnostic test. The test will begin by
indicating the letter P in every position followed by a countdown from 9 to 0 for each digit,
If this does not occur, disconnect power immediately and re-verify all wiring connections. If
the problem persists, contact ONICON.

J1

5

G

60HZ

1

J2-1

+15

+24

J2-12

G

G

10

R7

H3

R1

20075-50 REV. A

LED1

T1

D1

D2

VAR1

F1

TB1

D4

D3

H1

1

R1

20075-50 REV. A

F1

TB1

L1 N

Not Used

1/4 AMP

1/4 AMP

L1 N

Not Used

WARNING

Disconnect main power before proceeding.

!

!

WARNING

Connect the protective earth wire to the lug located in the lower left hand corner of the motherboard.

Protective Earth

Ground