3.3.2.5 Input Signal Connections from F-3100 & F-3200 Flow Meter

J1

5

G

60

HZ

1

J2-1

+15

+24

J2-12

G

G

10

R7

H3

R1

20075-50 REV. A

LED1

T1

D1

D2

VAR1

F1

1 AMP

TB1

D4

D3

H1

1

Analog Common -

* Frequency -

* Frequency +

4-20mA +

(B) Scaled +
(B) Scaled -

Flow Meter Inputs

* Shield

Auxiliary Flow Meter Signals

Earth

(A) Direction +

(A) Direction -

Terminal #

* (+) Pulse Output # 1

* (-) Pulse Output # 1

16
17

(+) Pulse Output # 2

(-) Pulse Output # 2

18
19

(+) 4-20mA Output

(-) 4-20mA Output

9

10

(+) Pulse Output # 2

(-) Pulse Output # 2

18
19

NOTE: The System-10 does not provide power to the F-3100 or F-3200 flow meter. Input power for the flow

meter must be provided separately. See flow meter manual for detailed wiring instructions.

Connections shown with * are required for all models. Connections shown with (A) are required for bi-directional

flow installations. Connections shown with (B) are for unidirectional installations.

Inputs &

Outputs

T4

1
2
3
4
5
6
7
8
9

10
11
12
13

T5

1
2
3
4
5
6

F-3100 and F-3200 Flow Meter

Terminal Connections

L1 N

Not Used

CAUTION

Shield and earth connections are required for proper operation. Failure to use shielded cable or

to connect earth to both the flow meter and System-10 may result in erratic operation. Shields

should be terminated at the System-10 shield terminals and left unterminated at the flow meter.

!

CAUTION

The System-10 internal 24 V power supply cannot provide power to the F-3100 or F-3200 flow meters.

!

3.3.2.4 Input Signal Connections From F-2600 & F-2700 Flow Meters

* 4-20mA -

* 4-20mA +

F-2600 Flow Meter

Connections

(A) Scaled +

(A) Scaled -

Flow Meter Inputs

* Shield

Auxiliary Flow Meter Signals

* Earth

Output

Terminals

Loop power +

Loop power -

Pulse out +
Pulse out -

* Earth

Connections shown with * are required for all installations. Connections shown with (A) are optional.