ONICON System-10 BTU User Manual

Page 33

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

System-10 BTU Meter Manual 03/15 - 0651-16 / 18323

Page

33

Top Turbine – This alarm will occur whenever zero pulses are accumulated from the top turbine

while simultaneously pulses are accumulating from the bottom turbine. To clear this alarm, the

flow meter should be physically inspected to determine why the top turbine is not rotating.


Bottom Turbine – This alarm will occur whenever zero pulses are accumulated from the bottom

turbine while simultaneously pulses are accumulating from the top turbine. To clear this alarm,

the flow meter should be physically inspected to determine why the bottom turbine is not

rotating.

System Reset Count – The last 3 digits on the display indicate the total number of system resets

that have occurred since the current version of the firmware was loaded.

5.3 TROUBLESHOOTING GUIDE FOR ONICON SYSTEM-10 BTU MEASUREMENT SYSTEM

NOTE: Also refer to the COMMISSIONING GUIDE located on the preceding pages.

REPORTED PROBLEM

POSSIBLE SOLUTIONS

For turbine meters -
No flow signal / energy rate
(while hydronic system is
active)

• Verify 24 VDC supply voltage to the flow meter.
• For insertion meters, verify the flow meter is correctly inserted

into the pipe (using depth gage).

• For insertion meters, verify that the flow meter electronics

enclosure is parallel with the pipe.

• Verify correct wiring to the flow meter (see wiring diagram).
• For turbine meters, check turbine(s) for clogging due to debris.
• If none of the above, check hydronic system to ensure that flow is

really present in the line.

• NOTE: Flow meter function cannot be verified by blowing on the

turbine(s). The sensing system requires a conductive liquid to
operate. You can test it by swirling it around in a bucket of water
and looking for the flow indicator LED to flash at the System-10.

Displayed flow rate too high,
too low, or does not change

• Verify pipe size. Contact ONICON if pipe size is different from

calibration tag.

• For insertion meters, verify that meter is inserted correctly into

the pipe (using depth gage).

• For insertion meters, verify that the flow meter electronics

enclosure is parallel with the pipe.

• For dual turbine meters, confirm that both turbines produce pulses.
• For turbine meters, check turbine(s) for debris.
• Verify supply voltages (to Btu meter and flow meter).
• Verify that the flow signal switch is in the run position (see

Section 5.1.2)

Displayed temperature(s) too
high or too low vs. expected
values

• Verify wiring to temperature sensor(s), including polarity.
• Verify that thermowells are inserted into the flow stream and that the

temperature sensors are completely inserted into the thermowells.


For technical assistance, contact ONICON at (727) 447-6140.

Advertising