Caution, Operating from 24 vac power – ONICON System-10 BTU User Manual

Page 17

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

System-10 BTU Meter Manual 03/15 - 0651-16 / 18323

Page

17

OPERATING FROM 24 VAC POWER

IMPORTANT NOTE

This option is not field selectable. Contact ONICON if you need to change the input voltage rating.

i

The SYSTEM-10 BTU Meter can be configured to operate from 24 ±4 V 50/60 Hz power.

Connect the 24 volt power source to the System-10 using the pre-drilled conduit or strain

relief opening located at the bottom of the enclosure. Do not connect the 24 volt source

until all signal connections have been made and verified. Connect 24 VAC wires to the

appropriate screw terminals as shown. Connect the protective earth wire as shown. Do not

exceed 13 in-lb (1.5 Nm) of torque when tightening.

As power is initially applied to the System-10, immediately confirm that the power light is

illuminated and the display is scrolling through the character diagnostic test. The test will

begin by indicating the letter P in every position followed by a countdown from 9 to 0 for

each digit. If this does not occur, disconnect power immediately and re-verify all wiring

connections. Contact ONICON if the problem persists.

!

J1

5

G

60

HZ

1

J2-1

+15

+24

J2-12

G

G

10

R7

H3

R1

20075-50 REV. A

LED1

T1

D1

D2

VAR1

F1

TB1

D4

D3

H1

1

R1

20075-50 REV. A

F1

TB1

3/4 AMP

3/4 AMP

L1 N

Not Used

L1 N

Not Used

CAUTION

This product must be connected to earth ground for proper operation. Failure to do so may result

in erratic operation.

Protective Earth

Ground