Flow meter inputs, Auxiliary flow meter signals, System-10 btu meter mother board – ONICON System-10 BTU User Manual

Page 49: Shield, Earth (green/ yellow), G60hz, Factory installed cable

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

System-10 BTU Meter Manual 03/15 - 0651-16 / 18323

Page A-15

SYSTEM-10 BTU METER MOTHER BOARD

F-3500 Insertion Electromagnetic

Flow Meter Input Connections

J1

5

G

60HZ

1

J2-1

+15
+24

J2-12

G
G

10

R7

H3

R1

20

075-50 REV. A

LED1

T1

D1

D2

VAR1

F1

1/8 AMP

TB1

D4

D3

H1

1

Connections shown for

T5-1 and

T5-2

are for the same analog output from the F-3500.

This output can be configured in

the flow meter as a 4-20m

A or 0 -10 VDC.

0-10 VDC + (Blue)

* Frequency - (

Yellow)

* 24VDC Supply + (Red)

* Supply Common - (Black)

* Frequency + (Green)

F-3500 Flow Meter Connections

Connections shown with * are required.

4-20m

A + (Blue)

Flow Meter Inputs

* Shield

Auxiliary Flow Meter Signals

Isolated

Analog Common - (Brown)

Earth (Green/

Yellow)*

Factory Installed Cable

T4

1

2

3

4

5

6

7

8

9

10

11

12

13

T5

1

2

3

4

5

6

Alarm - (White)

Alarm + (Orange)

Connections shown below dashed line are for flow meter output signals not used by the BTU meter

. Both incoming and

outgoing connections are made to the same terminal.

L1 N

Not Used