3.2 MECHANICAL INSTALLATION

3.2.1 Main Unit Installation

Find an easily accessible location where electrical

connections can be made and meter readings can be

taken from the floor level.

Mount the BTU meter on a vibration-free surface.

Avoid sites such as the plenum of a fan coil, heat

exchanger, or other housings containing motors.

Do not install the meter in direct sunlight.

i

IMPORTANT NOTE

The ONICON System-10 BTU Measurement System is a custom calibrated system. Unless

specifically noted in writing by ONICON, ALL COMPONENTS (Btu meter, flow meter and

temperature sensors) share the same serial number and must be installed together as a system.

Mixing components from different systems will result in significant errors in calibration.

2.500

1.750

1.750

3.250

3X 01.115

01.115

2.500

6.000

CONDUIT HOL LOCATION

BOTTOM VIEW

HINGE SIDE

SOWN FOR REFERENCE.

CONDUIT HOL LOCATION

RIGHT SIDE VIEW

!

CAUTION

DO NOT drill holes in the main unit. Use only the openings that are provided.