ONICON System-10 P1 User Manual

Page 27

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]

System-10-P1 Manual 10/14 - 0656-9 / 18320

Page 27

Powered Pulse:

This type of output refers to a pulse which has an associated voltage with it

(see Fig. 2). Set the selector switch, S1 to Pwrd Pulse. The allowable voltage range

is 5-24 VDC. The input impedance is set at the factory to be 11 KOHM via the

impedance selector jumper (J1, see Fig. 1). A lower impedance, 3 KOHM can be

selected if required by the instrument providing the pulse output. Consult the

instrument manufacturer or the ONICON Technical Department if you are uncer

tain as to the proper jumper selection.

Fig. 2

Open Collector (Sourcing):

This type of output refers to an open Collector Switch configured for a Sourcing

function (see Fig. 3). Set the selector switch, S1 to SRC. The switch must be rated

for at least 20mA at 20VDC.

Fig. 3

Di3 In (+)

Di3 In (-)

Di3 In (+)

Di3 In (-)

ONICON

BTU Meter

ONICON

BTU Meter

Advertising