11. Select the FLOW RATE

page. Note and record

the flow reading.

Scroll through the BTU meter display pages and select the FLOW RATE page.

Note the displayed flow rate and confirm that it is within the expected range

specified on the BTU meter certificate of calibration. Record the flow rate.

12. For flow meters that

provide a frequency

output, measure and

record output(s).

Compare calculated vs.

displayed flow rates.

F-1200 or FB-1200 only

Confirm both turbines

produce pulses.

The average frequency output signal is a 0-15 VDC pulsed output ranging up to

200 Hz and must be measured with a frequency counter or oscilloscope.

Measure DC Frequency (Hz) at T4 from terminal 6(+) to 7(-).

GPM = Frequency in Hz x 60

Meter Factor in ppg.

(Refer to calibration tag for meter factor.)

For the F-1200 or FB-1200 dual turbine model, also measure and record the top

and bottom turbine signals.

Top Turbine: T4-12(+) to T4-2(-). Bottom Turbine: T4-13(+) to T4-2(-)

Also, measure DC volts on same terminals. Five to 7 VDC is normal for a

spinning turbine. Zero or 14+ VDC indicates a stopped turbine. (1 to 4 VDC

could indicate a problem.)

13. Compare and record

the displayed values

with those shown by

the building control

system.

Scroll through each page of the BTU meter display menu and compare the

displayed values with those shown on the building control network. Record

the results.

End of standard commissioning. Please contact ONICON at (727)447-6140 with any questions.