11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]

System-10-P1 Manual 10/14 - 0656-9 / 18320

Page 33

TABLE OF STANDARD SYSTEM-10-P1 APPLICATION NUMBERS

1983

BTU/HR x 1,000,000

TON-HRS x 10

GAL x 10,000

GPM x 1

DEG F

1982

BTU/HR x 1,000,000

TON-HRS x 100

GAL x 1,000

GPM x 1

DEG F

1981

BTU/HR x 1,000,000

TON-HRS x 100

GAL x 10,000

GPM x 1

DEG F

1980

BTU/HR x 1,000,000

TON-HRS x 100

GAL x 10,000

GPM x 10

DEG F

1979

TONS x 1

BTU x 1,000

GAL x 10

GPM x 1

DEG F

1978

TONS x 1

BTU x 10,000

GAL x 10

GPM x 1

DEG F

1977

TONS x 1

BTU x 10,000

GAL x 100

GPM x 1

DEG F

1976

TONS x 1

BTU x 10,000

GAL x 1,000

GPM x 1

DEG F

1975

TONS x 1

BTU x 100,000

GAL x 100

GPM x 1

DEG F

1974

TONS x 1

BTU x 100,000

GAL x 1,000

GPM x 1

DEG F

1973

TONS x 1

BTU x 100,000

GAL x 10,000

GPM x 1

DEG F

1972

TONS x 1

BTU x 1,000,000

GAL x 1,000

GPM x 1

DEG F

1971

TONS x 1

BTU x 1,000,000

GAL x 10,000

GPM x 1

DEG F

1970

TONS x 1

BTU x 1,000,000

GAL x 10,000

GPM x 10

DEG F

1969

TONS x 1

TON-HRS x 1

GAL x 100

GPM x 1

DEG F

1968

TONS x 1

TON-HRS x 1

GAL x 1,000

GPM x 1

DEG F

1967

TONS x 1

TON-HRS x 10

GAL x 1,000

GPM x 1

DEG F

1966

TONS x 1

TON-HRS x 10

GAL x 10,000

GPM x 1

DEG F

1965

TONS x 1

TON-HRS x 100

GAL x 1,000

GPM x 1

DEG F

1964

TONS x 1

TON-HRS x 100

GAL x 10,000

GPM x 1

DEG F

1963

TONS x 1

TON-HRS x 100

GAL x 10,000

GPM x 10

DEG F

4.6 SYSTEM-10-P1 POINT DATABASE

The Point Database table on the next page lists all of the points used by the System-10-P1 BTU

Meter. NOTE: Also refer to the Siemens’ Application Note, Document No. 140-0280 for more

information.

4.6.1 System-10-P1 Point Database

i

IMPORTANT NOTE

System-10-P1 BTU Meter totalization registers are 6 digit registers. User defined units and

multipliers are then applied to these values. This is required to allow for the accumulation of totals

over a reasonable time period without exceeding the capacity of the register. P1 variables are limited

in range to 32,767. In order to properly convey the System-10-P1 information, each totalization

register is represented by two separate type 3 LAI points. The first point represents digits from

0-9,999. The second point represents the digits from 10,000-999,999. The user-selected multiplier is

applied to the units for the first word. For the second point, the multiplier is adjusted by a factor of

10,000 then applied to the units.

Example: The System-10-P1 would process a Mode 1 Energy Total of 500,100,000 Btu’s, as 500,100

x 1K BTU. The associated P1 variables would be as follows:

• Point 9 – 0100, Units x 1kBtu

• Point 10 – 0050, Units x XMBtu