3.2.4 Flow Meter Installation

Determine which pipe (supply or return) has the longer unobstructed straight run. Install

the flow meter in the longest straight pipe run available. One temperature sensor can be

installed five diameters downstream of the flow meter leaving enough clearance to remove

either sensor from the pipe without interference from the other sensor.

Also refer to the installation manual and/or other documentation that is provided with

your ONICON flow meter.

For F-1300 series inline turbine flow meters, refer to the documentation that is provided

with the flow meter.

ONICON TEMPERATURE SENSOR

TEMPERATURE SENSOR INSTALLED IN THERMOWELL