Super Systems Compact HMI User Manual

Page 16

Advertising
background image

Compact HMI and Compact HMI Editor Operations Manual

Super Systems Inc.

Page 16 of 60

Connection types can be changed after a

connection is defined. To do this, right

click on the Connection Name, select

“Change Connection Type”, and select the

Connection Type desired. See an example

in Figure 15.

Figure 15 - Change Connection Type option

The Edit menu allows you to copy an existing connection or tag with all of its properties and bit

settings. Do this by first selecting the item you want to copy, then click Copy in the Edit menu,

and then click Paste in the Edit menu. The new (copied) item will be added to the tags list as

ItemName

Copy(

number

)”. Using the Edit menu’s Delete option, you can remove an item.

Finally, using the Find & Replace option, you can direct Compact HMI Editor to search for a

specific string of text in tag names and replace that text names with text that you enter.

The Sort menu allows you to order connection names and tags alphabetically (by name) or by

address (in the case of tags, that is the register address associated with the tag). Sorting can be

performed in ascending or descending order.

Using the tag properties grid, you can name the tag set

and address offset, and enter a brief description. See

Figure 16.

The default name of the tag will be “NewTag

x”,

where

x

is a sequential number. The Address Offset will be

applied to the Data Offset previously assigned to the

Panel. For example, referring to Figure 9 and Figure

16, if a Data Offset of N7:0 and Address Offset of 4 are

defined, the actual register being evaluated will be

N7:4.

Figure 16 - Tag "Data" fields

Each register is made up of 16 bits. The bits are

numbered 0 through 15. Compact HMI Editor allows

you to name each bit, add a brief description, and

identify whether the bit is an alarm bit (see Figure 17).

If “Is Alarm Bit” is set to False, Compact HMI will not

identify the bit as an alarm bit; if “Is Alarm Bit” is set to

True, then Compact HMI will identify the bit as an

alarm bit. The default setting for this field is False.

This feature is intended for future use.

Figure 17 - Bit fields

Once configured, tags are used with Compact HMI’s control objects to help determine display

conditions and other characteristics of a control system.

Advertising