Figure 8-4. fault 2, shorted thermocouple -6, Hazardous area oxymitter 4000, Alarms o2 t/c shorted – Emerson Process Management OXYMITTER 4000 User Manual

Page 102: Instruction manual

Advertising
background image

Instruction Manual

IB-106-340C Rev. 4.1
July 2004

8-6 Troubleshooting

Rosemount Analytical Inc. A Division of Emerson Process Management

Hazardous Area Oxymitter 4000

Alarms

O2 T/C Shorted

LOI

KEYPAD

DIAGNOSTIC

ALARMS

TEST

POINTS

HEATER T/C

HEATER

O2 CELL

CALIBRATION

CALIBRATION RECOMMENDED

O2 CELL mV +

O2 CELL mv -

HEATER T/C +

HEATER T/C -

INC

INC

DEC

DEC

HIGH

GAS

LOW

GAS

CAL

TEST GAS +

PROCESS -

% O2

SW2

TP1

J1

TP2

TP3

RED

YEL

GRN

ORG

TP4

TP5

TP6

ON

37260020

Figure 8-4. Fault 2, Shorted Thermocouple

b. Fault 2, Shorted Thermocouple

Figure 8-4 shows the electronic assembly

for a Hazardous Area Oxymitter 4000 with
a membrane keypad (upper view) and a
Hazardous Area Oxymitter 4000 with an
LOI (lower view). The upper view also
shows J1 and test points TP1 through TP6,
located on the microprocessor board, below
the membrane keypad or the LOI module.

Membrane Keypad. When Fault 2 is

detected, the HEATER T/C LED flashes
twice, pauses for three seconds, and
repeats.

1. Using a multimeter, measure the volt-

age from TP3+ to TP4-. If the reading
is 0 ±0.5 mV, then a shorted thermo-
couple is likely.

2. Remove power and disconnect J1.

3. Measure the resistance from TP3+

to TP4-. The reading should be ap-
proximately 20K ohms.

4. If so, the short is not on the PC board.

The thermocouple wiring or the ther-
mocouple is shorted. See paragraph
9-4g, Heater Strut Replacement.

LOI. When Fault 2 is detected, the LOI

displays the “O2 T/C Shorted” message.

1. Remove power. Unscrew and remove

the LOI module from the electronic
assembly.

2. Reconnect power to the Oxymitter

4000.

3. Perform the diagnostic steps 1 through

4 shown for the membrane keypad.

Advertising