Configuration with LOI 4-3

Hazardous Area Oxymitter 4000

f. Once the cell is up to operating tempera-

ture, the O

2

percentage can be read:

1. To access TP5 and TP6 under the LOI

module (Figure 4-2), power down the
Oxymitter 4000 and remove the LOI
module. Attach alligator leads from a
multimeter across TP5 and TP6
(Figure 3-2). Install the LOI module and
power up the Oxymitter 4000. Allow
time for the cell to reach operating
temperature. The calibration and proc-

ess gases can now be monitored.
When a calibration has been initiated,
the value at TP5 and TP6 is the % O

2

seen by the cell. Oxygen levels, as
seen on the multimeter, are:

8.0% O

2

= 8.0 VDC

0.4% O

2

= 0.4 VDC

2. HART/AMS.

3. Model 751. The loop-driven LCD

display.

SW2

SW1

1

2
3
4

TP1

J1

TP2

TP3

RED

YEL

GRN

ORG

TP4

TP5

TP6

4-20 mA

IS INTERNALLY

POWERED

(DEFAULT)

4-20 mA REQUIRES
EXTERNAL POWER

HART

0 TO 10% O

2

3.5 mA

220 V

115 V

0 TO 25% O

2

LOCAL

21.6 mA

DEFAULT

POSITION

(EX-FACTORY)

3.5 mA/21.6 mA:

0 TO 25% O :

2

0 TO 10% O /

2

LOCAL:

HART: O RANGE SET BY HART/AMS

(FROM 0 TO 40% O )
O RANGE SET BY POS 2

O RANGE
WHEN ALARM EXISTS, OR
ON POWER UP, CURRENT
OUTPUT GOES TO THIS VALUE

2

2

2

2

37270011

ON

OFF

NOTE:

THE 115 V OPTION
AT SWITCH SW2
POSITION 4 IS ACTIVE
ONLY WHEN THE
HEATER VOLTAGE
OPTION IS SET TO
MANUAL IN THE
SOFTWARE.

Figure 4-2. Defaults – Hazardous Area Oxymitter 4000 with LOI