Hazardous area oxymitter 4000, Instruction manual – Emerson Process Management OXYMITTER 4000 User Manual

Page 70

Advertising
background image

Instruction Manual

IB-106-340C Rev. 4.1
July 2004

4-2 Configuration with LOI

Rosemount Analytical Inc. A Division of Emerson Process Management

Hazardous Area Oxymitter 4000

c.

Verify Hazardous Area Oxymitter 4000
Configuration

Located on the microprocessor board are

two switches that configure Hazardous
Area Oxymitter 4000 outputs (Figure 4-2).
To access these switches, the LOI module
must be removed. SW1 determines if the
4-20 mA signal is internally or externally
powered. SW2 determines:

The HART option is not protected by
energy limiting barriers. It must not be
interfaced from within the hazardous
area. The 4-20 mA cables should be
routed and the connections made out-
side the hazardous area. Note that this
is the case even when using the intrin-
sically safe version of the handheld
communicator.

1. Hazardous Area Oxymitter 4000

status, HART or LOCAL.

2. Oxygen range, 0 to 10% O

2

or 0 to

25% O

2

. (0 to 40% O

2

is also configur-

able only through HART/AMS.)

3. The 4-20 mA signal, at fault or power

up, 3.5 mA or 21.6 mA.

Remove power from the Hazardous
Area Oxymitter 4000 before changing
defaults. If defaults are changed under
power, damage to the electronics
package may occur.

d. SW1

The two settings are internally or externally

powering the 4-20 mA signal. The factory
setting is for the 4-20 mA signal to be inter-
nally powered.

e. SW2

The factory sets this switch as follows:

1. Position 1 is HART/LOCAL. This switch

setting controls the configuration of the
Hazardous Area Oxymitter 4000. The
defaults cannot be changed via
HART/AMS or the LOI unless the
switch is in the HART position. Placing
SW2, position 1 in the LOCAL position
forces the O

2

range to the setting of

position 2. The position 1 switch must
be in the LOCAL position or changes in
SW2, position 2 will have no effect.

2. Position 2 determines the O

2

range.

This can be set to either 0 to 10% O

2

or 0 to 25% O

2

. The factory setting is

0 to 10% O

2

.

Typically, the probe’s sensing cell, in
direct contact with the process gases,
is heated to approximately 736°C
(1357°F). The external temperature of
the probe body may exceed 450°C
(842°F). If operating conditions also
contain high oxygen levels and com-
bustible gases, the Hazardous Area
Oxymitter 4000 may self-ignite.

If necessary, the O

2

range can be con-

figured from 0 to 40% O

2

. To select

values within this range, set SW2,
position 1 to HART and then enter the
range via HART/AMS or the LOI. Do
not change SW2, position 1 to LOCAL
unless you want to operate in the
range specified by SW2, position 2.

3. Position 3 determines the output at

startup or at an alarm. The settings are
3.5 mA or 21.6 mA. The factory setting
is 3.5 mA. At startup, the current at the
analog output is 3.5 mA or 21.6 mA.

4. Position 4 can be used to set the

heater for 115 or 220 Vac operation.
This switch is functional only when the
software is set for manual voltage
selection (Auto Tune = No). Otherwise,
the internal electronics auto detect the
input line voltage and sets the heater
voltage accordingly (Auto Tune = Yes).

Advertising