3-1 check the engine speed, 3-3 check the appliance for trouble, 3-4 check if the engine is overheated – Subaru Robin RGD3300H User Manual

Page 49: 3-5 check the insulation of the generator

Advertising
background image

– 46 –

10-3 AC VOLTAGE IS NORMAL AT NO-LOAD, BUT THE LOAD CANNOT BE APPLIED.

10-3-1 CHECK THE ENGINE SPEED.

If the engine speed is low, adjust it to the rated r.p.m.

* Refer to Step 10-2-1 for engine speed adjustment.

10-3-2 CHECK THE TOTAL WATTAGE OF APPLIANCES CONNECTED TO THE GENERATOR.

Refer to Section 6. “RANGE OF APPLICATIONS” for the wattage of the appliances.
If the generator is over-loaded, reduce the load to the rated output of the generator.

10-3-3 CHECK THE APPLIANCE FOR TROUBLE.

If the appliance is faulty, repair it.

10-3-4 CHECK IF THE ENGINE IS OVERHEATED.

If the cooling air inlet and/or cooling air outlet is clogged with dirt, grass, chaff or other debris, remove it.

10-3-5 CHECK THE INSULATION OF THE GEN-

ERATOR.

Stop the engine. Measure the insulation resistance
between the live terminal of the receptacle and the
ground terminal.

If the insulation resistance is less than 1 M

Ω, disas-

semble the generator and check the insulation
resistance of the stator, rotor and the live parts in
the control box. (Refer to Section 7-3.)

Any part where the insulation resistance is less
than 1 M

Ω, the insulation is faulty and may cause

electric leakage.

Replace the faulty part.