Restricting snmp access, System location and system contact – Eaton Electrical 1000 User Manual

Page 27

Advertising
background image

CONFIGURING THE CARD

EATON Power Xpert

®

Gateway Series 1000 Card User’s Guide

S 164201670 Rev 1

23

4.

Click Apply and then OK to save the settings.

5.

Repeat Steps 3 and 4 for each additional trap recipient.

To remove a trap recipient, click Delete Last. Click OK when
prompted to remove the settings for the trap recipient entered last.

Restricting SNMP Access

To limit access to the card from trusted SNMP NMS hosts only:

1.

From the card’s Web page, click the Access Control link from the
menu bar.

2.

Activate the check box for SNMP access restricted by IP/hostname.

3.

Type the trusted NMS host’s IP addresses or host names,
separated by a semi-colon, in the Trusted IPs/hostnames field.

NOTE When using host names, verify that the IP address of your network DNS Server is
configured (see “Network Configuration” on page 16).

4.

Click Apply and then OK to save the settings.

System Location and System Contact

To set the system location and system contact:

1.

From the card’s Web page, click the Network link from the menu
bar.

2.

Enter the physical location of the installed Power Distribution Unit
(PDU)/card (sysLocation string) in the System location field. This
value also appears in the card’s Web page header bar.

3.

Enter the information to identify someone to contact with questions
about this device (sysContact string) in the System contact field. For
example, you can type a person’s name, phone number,
department, e-mail address, physical location, or combination of
these items, such as “John Smith x123”.

4.

Click Apply and then OK to save the settings.