Environmental Monitoring Probe (FC 03 or 04)

The optional Environmental Monitoring Probe for the PDU/RPP can
measure temperature and humidity. Because the device can be located
outside the PDU/RPP, the reference is to “auxiliary” data. In addition, it
contains two connections for monitoring the condition of auxiliary input
contacts, such as a door switch. See Table 9 for a list of EMP registers.

An exception code is returned if the EMP is not installed.

To read the temperature at the PDU/RPP, set the Modbus program to
Unit ID 254 and coil address 12028:

IP: <IP address of PDU/RPP>
Unit ID: 254
Starting Register: 12028
Number of registers: 2
Function Code: 04

Table 9. Environmental Monitor (FC 03 or 04)

Name

Register

Data Type

Bytes

Vendor Name

1001

STRING

64

Model Name

1033

STRING

64

Display Name

1065

STRING

64

Serial Number

1123

STRING

64

Device ID

1099

UINT

4

Auxiliary Input 1

10275

UINT

2

Auxiliary Input 2

10276

UINT

2

Auxiliary Temperature

12028

FLOAT

4

Auxiliary Humidity

12030

FLOAT

4