Configuring emp settings – Eaton Electrical 1000 User Manual

Page 32

Advertising
background image

CONFIGURING THE CARD

EATON Power Xpert

®

Gateway Series 1000 Card User’s Guide

S 164201670 Rev 1

28

Configuring EMP Settings

NOTE Verify that the Power Xpert Gateway Card DIP switch #2 is set to the ON position,
enabling the card for communication with an EMP.

To configure the EMP settings:

1.

From the card’s Web page, click the Environmental Monitoring Probe
link from the menu bar.

2.

For Contact #1 and #2, enter the Contact Description, such as
External Contact #1 and External Contact #2.

3.

For Contact #1 and #2, select the Contact Type as Normally Open or
Normally Closed from the pull-down menu. Disabled is the default.

4.

To set the temperature limits of the EMP, enter 0 to 70 degrees
Celsius for the Temperature Upper Limit and the Temperature Lower
Limit
. The default for the upper limit is 70; the default for the lower
limit is 0.

5.

Use the Temperature Hysteresis to control the alarm when the
current value is hovering around the limit. When the EMP
temperature measure activates the alarm, it can come out of the
alarm state only by dropping below the Temperature Hysteresis
value. Enter a value between 0 and 10 percent. The default is
2 percent.

6.

To set the humidity limits of the EMP, enter 0 to 90 percent for the
Humidity Upper Limit and the Humidity Lower Limit. The default for the
upper limit is 90; the default for the lower limit is 0.

7.

Use the Humidity Hysteresis to control the alarm when the current
value is hovering around the limit. When the EMP humidity
measure activates the alarm, it can come out of the alarm state only
by dropping below the Humidity Hysteresis value. Enter a value
between 0 and 20 percent. The default is 2 percent.

8.

Click Apply to save the settings.

Advertising