Panel alarms (fc 01 or 02) – Eaton Electrical 1000 User Manual

Page 67

Advertising
background image

MODBUS REGISTERS

EATON Power Xpert

®

Gateway Series 1000 Card User’s Guide

S 164201670 Rev 1

63

Table 5. Panel Summary Registers (FC 04) (continued)

Bytes

Data Type

Register

Name

MIN Frequency

11022

FLOAT

4

MAX Frequency

11027

FLOAT

4

Panel Alarms (FC 01 or 02)

Table 6 lists the panel alarms. They are not registers, but are discrete
inputs and are read using FC 01 or FC 02.

To read the Main Breaker Overload alarm at Panel #4, set the Modbus
program to Unit ID 5 and coil address 1254:

IP: <IP address of PDU/RPP>
Unit ID: 5
Starting Register: 1254
Number of Registers: 1
Function Code: 02

Table 6. Panel Alarms (FC 01 or 02)

Name

Coil/Status Address

Data Type

Neutral Overload

1219

BOOL

Panel Under Voltage

1238

BOOL

Panel Over Voltage

1242

BOOL

Panel Under Over Frequency

1248

BOOL

Branch Breaker Overload Warning

1249

BOOL

Branch Breaker Overload

1250

BOOL

Main Breaker Overload Warning

1253

BOOL

Main Breaker Overload

1254

BOOL