MODBUS REGISTERS

EATON Power Xpert

®

Gateway Series 1000 Card User’s Guide

S 164201670 Rev 1

54

PDU/RPP Registers and Alarms

This section contains information for the PDU/RPP Registers (FC 04) and
PDU/RPP Alarms (FC 02).

PDU/RPP Registers (FC 04)

To read the vendor name in the PDU/RPP, set the Modbus program to
Unit ID 1 and register 1001:

IP: <IP address of PDU/RPP>
Unit ID: 1
Starting Register: 1001
Number of registers: 32
Function Code: 04

The PDU/RPP returns 32 registers containing up to 64 characters. There
are two ASCII characters per register, so the vendor name could be
displayed as POWERWARE.

Table 3. PDU/RPP Registers (FC 04)

Name

Register

Data Type

Bytes

Vendor Name

1001

STRING

64

Model Name

1033

STRING

64

Display Name

1065

STRING

64

Device Type

1097

UINT

4

Device ID

1099

UINT

4

Device Guid

1103

STRING

40

Serial Number

1123

STRING

64

Conn Style

1159

UINT

2

Device Comm Address

1160

STRING

64

Device Baud Rate

1192

UINT

4

Time Sync Period

1194

UINT

4

Data Update Period

1196

UINT

4

Device VAR Rating

1198

UINT

4

Device Volts In Rating

1204

UINT

4

Device Volts Out Rating

1206

UINT

4