Breaker data and alarms, Breaker #1 data registers (fc 04) – Eaton Electrical 1000 User Manual

Page 68

Advertising
background image

MODBUS REGISTERS

EATON Power Xpert

®

Gateway Series 1000 Card User’s Guide

S 164201670 Rev 1

64

Breaker Data and Alarms

This section contains:

S

Names of breaker parameters along with the register numbers for
Breaker #1

S

Instructions for calculating the register numbers for other breakers

S

Breaker alarms

Breaker #1 Data Registers (FC 04)

To specify a specific breaker, use a Unit ID for breaker data along with
the register number for the specific breaker.

For example, “Watts in Phase A” is register 1055 for Breaker #1. This
statement is true for any panel. To specify a specific panel for breaker
data, use the panel’s Unit ID in the Modbus program. For Panel #6
(Unit ID 23), the Modbus program would be set as follows:

IP: <IP address of PDU/RPP>
Unit ID: 23
Starting Register: 1055
Number of registers: 2
Function code: 04

The Modbus program would return a value of the watts in Phase A for
Breaker #1 in Panel #6 of the PDU/RPP at the specified IP address.

Table 7. Breaker #1 Data Registers (FC 04)

Name

Register

Data Type

Bytes

Display Name

1000

STRING

64

Number of Phases

1032

UINT

2

Breaker Rating

1033

UINT

4

Breaker Warning

1035

UINT

2

Breaker Overload

1036

UINT

2

AC Current Phase A

1037

FLOAT

4

AC Current Phase B

1039

FLOAT

4

AC Current Phase C

1041

FLOAT

4

AC MAX Current Phase A

1043

FLOAT

4

AC MAX Current Phase B

1045

FLOAT

4