Chapter 14 product specifications, 1 model numbers, 2 ups system input – Eaton POWERWARE 9315 User Manual

Page 107

Advertising
background image

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201691 Rev 1 www.powerware.com

14-1

Chapter 14

Product Specifications

The following sections detail the input, output, environmental, and battery
specifications for the UPS.

14.1

Model Numbers

The UPS systems are housed in free-standing, double-front cabinets with safety
shields behind the doors. The UPS systems are available in 50/60 Hz with various
output power ratings. Smaller models within a system may be upgraded in the field to
larger models:

System

Models

Notes

Powerware 9315-625

562, 500, 450, 400 kW

50/60 Hz

Powerware 9315-750

675, 600, 562, 500 kW

60 Hz only

14.2

UPS System Input

Operating Input Voltage
(Nominal +10/–15%)

600 Vac for operation from 510 Vac to 660 Vac (60 Hz only)
480 Vac for operation from 408 Vac to 528 Vac (60 Hz only)
400 Vac for operation from 340 Vac to 440 Vac (50/60 Hz only)

Operating Input Frequency
Range

3 Hz of nominal (50 Hz or 60 Hz)

Operating Input Current

Battery Charge
125% of full load for overload + battery charge

Actual load + 25% of full load for battery charge with 0.8 pF
output units

115% of full load for overload + battery charge

Actual load + 15% of full load for battery charge with 0.9 pF
output units

Reduced for Generator
Adjustable, set to 102%

Input Current Harmonic
Content

5% THD at full load (with input filter option installed)

Power Walk-In

Adjustable 3–60 second rectifier ramp-up to full utility load

Power Factor

Minimum 0.85

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4

Figure 14Table 14