INSTALLATION REFERENCE

EATON Powerware

®

9315 UPS (500–750 kVA) Installation and Operation Manual

S 164201691 Rev 1 www.powerware.com

A-2

6.

The basic environmental requirements for UPS system operation are:

S

Ambient Temperature Range:

0–40°C (32–104°F)

S

Recommended Operating Range: 20–25°C (68–77°F)

S

Maximum Relative Humidity:

95%, noncondensing

The UPS ventilation requirements are shown in Table C.

Table C. Air Conditioning or Ventilation Requirements During Full Load Operation

Rating

Input/Output Voltage

Heat Rejection

BTU/hr

¢ 1000/hr (kg-cal/hr)

Ventilation Required for

Cooling Air Exhaust

500 kVA

400/400

109 (27.5)

625 kVA

400/400

130.8 (33)

1420 liter/sec

625 kVA

480/480, 600/600

109 (27.5)

1420 liter/sec

(3000 cfm)

750 kVA

480/480, 600/600

130.8 (33)

MBC

Output/Inverter

Cabinet

Input/Rectifier

Cabinet